H8000
TYPE BOXES FOR CLASS II, (GROUPS E, F, and G) HAZARDOUS
LOCATIONS
Class II, Groups E, F and G hazardous locations are ones
in which explosive mixtures of air with metal dust (Group
E), or carbon, coke or coal dust (Group F), or grain dust
(Group G), are encountered. Enclosures with adequate flanges,
mechanically held gaskets of proper composition, and bossed
and tapped conduit entrances with five threads will meet
Class II requirements.
All H8000 type boxes listed above will conform to these
requirements when ordered specifically as follows:
(1) With gasket of vellumoid: Specify "Mechanically
Attached" (Extra 10%)
(2) With bossed and tapped conduit entrances of five threads
Mounting Lugs
(3) Mounting lugs are optional, but mounting holes through
box are not permissible.
See further listing on Class II boxes, under Metal
Pipe amd Pole Bases and under Explosion
Housing.
H5400
and H5600 type and H6000 type boxes for CLASS I, GROUPS
C and D hazardous location are listed under
Explosion Housing.
|